高压线对机场全向信标及测距仪的电磁干扰分析
DOI:
CSTR:
作者:
作者单位:

中国民用航空飞行学院,广汉 618307

作者简介:

通讯作者:

中图分类号:

V219

基金项目:

中央高校建设世界一流大学(学科)和特色发展引导专项资金(D202103)资助


Analysis of electromagnetic interference of high voltage line to omnidirectional beacon and rangefinder in airport
Author:
Affiliation:

Civil Aviatiom Flight University of China,guanghan 618307, China

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    为了研究高压输电线对机场终端全向信标和DME测距仪信号的影响,选取某机场附近的高压输电线对其产生的电磁辐射进行了实际测试。通过控制和改变计算模型中参数的方法,研究了输电线路对VOR/DME信号的电磁干扰影响规律,得出飞机接收信号受高压线电磁干扰最大位置,依据电波传播的原理和国标有关规定,对在此位置的VOR/DME信号进行电磁干扰影响分析。结果表明,此处飞机能够接收到的VOR信号信噪比为42.7dB,符合国标规定的最低20dB的要求;DME信号的信噪比为97.3db,符合国家标准。在此基础上计算出高压输电线对机场VOR/DME台站的防护距离,提出了高压输电线路与机场范围VOR/DME台站的有源干扰防护距离建议。本文研究成果能够为机场附近高压输电线和机场区域通信导航监视等无线电设备的电磁兼容性设计提供依据。

    Abstract:

    In order to study the influence of the high voltage transmission lines near the airport on the reception of VOR(Very High Frequency Omnidirectional Range) and DME(Distance Measuring Equipment) signal, test the electromagnetic radiation generated by the high voltage transmission lines near the airport. By controlling and changing the parameters in the calculation model, study the influence law of the transmission line on the electromagnetic interference of aircraft airborne signals, and obtain the maximum height of the aircraft subjected to high-voltage wire EMI(Electromagnetic Interference). According to the radio wave propagation theory and the relevant provisions of national standard, analyze the influence of electromagnetic interference on the airborne signals at this position .The SNR(Signal to Noise Ratio)of the VOR signal received by the aircraft at the maximum height of EMI is 42.7dB, Comply with the requirements of the national standard minimum which is 20dB. DME signal signal-to-noise ratio is 97.3dB, in line with the national standard.On this basis, calculate the protective distance of the high voltage transmission line to the airport VOR/DME station , and propose the suggestion of active interference protection distance between the range of the high voltage transmission line and the airport VOR/DME station .The research results in this paper can provide a basis for the electromagnetic compatibility design of high voltage transmission lines and radio equipment such as airport communication, navigation and surveillance.

    参考文献
    相似文献
    引证文献
引用本文

程擎,但诗芸,鲁合德.高压线对机场全向信标及测距仪的电磁干扰分析[J].电子测量技术,2021,44(18):13-18

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2024-08-09
  • 出版日期:
文章二维码