基于微波透射法的输变电钢筋混凝土腐蚀检测
DOI:
CSTR:
作者:
作者单位:

1.国网浙江省电力有限公司武义供电公司 金华 321200; 2.浙江武义电气安装工程有限公司 金华 321200; 3.湖北省输电线路工程技术研究中心(三峡大学) 宜昌 443002; 4.三峡大学电气与新能源学院 宜昌 443002

作者简介:

通讯作者:

中图分类号:

TU529.33

基金项目:

国网浙江省电力有限公司科技项目(BD60ZHJS20 20001)、国家自然科学基金 (51807110)项目资助


Corrosion detection of reinforced concrete for power transmission and transformation based on microwave transmission method
Author:
Affiliation:

1.State Grid Zhejiang Wuyi Electric Power Supply Company,Jinhua 321200, China;2.Zhejiang Wuyi Electric Installation Engineering Co., Ltd.,Jinhua 321200, China;3.Hubei Provincial Engineering Technology Research Center for Power Transmission Line, China Three Gorges University,Yichang 443002, China;4.College of Electrical Engineering & New Energy, China Three Gorges University,Yichang 443002, China

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    为更好地评估输变电钢筋混凝土结构质量安全,提出了基于微波透射法的输变电钢筋混凝土结构腐蚀检测方法,开展了钢筋通电加速腐蚀试验,获得了不同腐蚀程度钢筋混凝土模型;搭建了微波检测试验平台,通过对不同腐蚀程度钢筋混凝土模型进行微波无损检测,分析了透射系数S21幅值和相位的变化规律。结果表明:湿盐沙环境下通电加速腐蚀试验能在较短时间内获得不同腐蚀程度的钢筋;当提离距离为4 mm时,通过透射系数S21幅值和相位变化趋势可有效识别混凝土内部钢筋腐蚀状态。研究可为输变电钢筋混凝土结构腐蚀检测提供参考。

    Abstract:

    To better evaluate the quality and safety of reinforced concrete structures used in power transmission and transformation, a corrosion detection method was proposed for reinforced concrete structures in power transmission and transformation based on the microwave transmission method. The accelerated corrosion test of steel bars was carried out, and reinforced concrete models with different corrosion degrees were obtained. A microwave detection test platform was built. The variation of the amplitude and phase of the transmission coefficient S21 was analyzed through microwave nondestructive testing of reinforced concrete models with different degrees of corrosion. The results show that the accelerated corrosion test in a wet salt sand environment can obtain steel bars with different corrosion degrees in a short time. When the lift-off distance is 4 mm, the corrosion state of steel bars in concrete can be effectively identified by the amplitude and phase change trend of transmission coefficient S21. The research can provide a reference for corrosion detection of power transmission and transformation-reinforced concrete structures.

    参考文献
    相似文献
    引证文献
引用本文

王申华,林军,喻红林,黎子晋,黎鹏,吴田.基于微波透射法的输变电钢筋混凝土腐蚀检测[J].电子测量技术,2023,46(22):56-61

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2024-03-08
  • 出版日期:
文章二维码