级联H桥变换器主动热控制下的谐波性能优化
DOI:
CSTR:
作者:
作者单位:

1. 国网浙江省电力有限公司经济技术研究院,杭州 310000;2. 国网浙江省电力有限公司湖州供电公司,湖州 313000; 3. 国网浙江省杭州市富阳区供电公司,杭州 311400;4. 浙江大学,电气工程学院,杭州 310063

作者简介:

通讯作者:

中图分类号:

TM46

基金项目:

国家自然科学基金青年项目(51807173)、中央高校基本科研业务费专项资金项目(2021QNA4012)资助


Harmonic performance optimization for cascaded H-bridge converter under active thermal control
Author:
Affiliation:

1. Research Institute of Economics and Technology, State Grid Zhejiang Electric Power Co., Ltd., Hangzhou 310000, China; 2. Huzhou Power Supply Company, State Grid Zhejiang Electric Power Co., Ltd., Huzhou 313000, China; 3. State Grid Fuyang District Power Supply Company, Huzhou 311400, China; 4. School of electrical engineering, Zhejiang University, Huzhou 310063, China

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    针对级联H桥变换器主动热控制下不平衡运行时,钳位H桥模块在两倍载波频率附近产生大量谐波的问题,提出了一种级联H桥变换器主动热控制下的谐波性能优化策略。深入分析了变换器中钳位H桥模块热控制下输出电压的谐波失真,设计了基于H桥模块载波角来修正非常规PSPWM以消除了两倍载波频率边带谐波。利用级联H桥变换器样机开展了实验,测试结果为,采用谐波性能优化控制后,两倍载波频率附近主导谐波被消除,同时钳位H桥模块温度降低0.9℃。测试结果表明,主动热控制下的新型谐波性能优化策略可有效提高级联H桥变换器系统输出谐波性能,并实现H桥模块热均衡。

    Abstract:

    When the cascaded H-bridge converter operates unbalanced under active thermal control, the clamping H-bridge module generates a large number of harmonics around twice the carrier frequency. Aiming at this problem, a harmonic performance optimization strategy under active thermal control of the cascaded H-bridge converter is proposed. The harmonic distortion of the converter output voltage with the clamped H-bridge module under thermal control is analyzed in-depth, and an unconventional PSPWM based on the carrier angles correction of the H-bridge module is designed to eliminate the sideband harmonics of the double carrier frequency. Experiments were carried out using a prototype of the cascaded H-bridge converter, and the test result is that after adopting the harmonic performance optimization control, the dominant harmonics around twice the carrier frequency were eliminated, and the temperature of the clamping H-bridge module was reduced by 0.9°C. The test results show that the novel harmonic performance optimization strategy under the active thermal control can effectively improve the output harmonic performance of the cascaded H-bridge converter system and realize the thermal equilibrium of the H-bridge modules.

    参考文献
    相似文献
    引证文献
引用本文

戴 攀,邹 波,陈家乾,朱小军,叶承晋.级联H桥变换器主动热控制下的谐波性能优化[J].电子测量技术,2021,44(14):84-90

复制
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:
  • 最后修改日期:
  • 录用日期:
  • 在线发布日期: 2024-09-05
  • 出版日期:
文章二维码